Specifications

990-4618C-001 InRow Chilled Water Air Conditioners Technical Specifications 81
*Capacity rated at the following conditions:
EFT: 50F (10C) / CW Delta T 6.6°C (12°F)—ACRC301S
EFT: 59F (15C) / CW Delta T 6.6°C (12°F)—ACRC301H
EFT: 45F (7.2C) / CW Delta T 6.6°C (12°F)—ACRC500/ACRP500 Series
**Optional: NEMA L21-20P
***Optional: NEMA IEC-309 16A
****Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
†Plug connection can only be top wired. Hardwired can be done via the top or bottom of the unit.
Optional Filter Type
2-in.
Pleated
2-in.
Pleated
4-in
Pleated
4-in
Pleated
4-in
Pleated
4-in
Pleated
4-in
Pleated
4-in
Pleated
Optional Filter Efficiency 30% 30% 85% 85% 85% 85% 85% 85%
Condensate Pump Included N/A Included Included Included Included Included Included
Humidifier Type N/A N/A N/A N/A N/A
Steam
Canister
Steam
Canister
Steam
Canister
Reheat Type N/A N/A N/A N/A N/A
S/S Finned
Tubular
S/S Finned
Tubular
S/S Finned
Tubular
Rack Inlet Temperature Sensor Quantity 1 1 3 3 3 3 3 3
Piping Connections
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
Electrical Connections
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
Top
or
Bottom
CW Flow Meter Included Included Included Included Included Included Included Included
Cable Type Water Detector Optional Optional Optional Optional Optional Optional Optional Optional
Model
ACRC
301S
ACRC
301H
ACRC
500
ACRC
501
ACRC
502
ACRP
500
ACRP
501
ACRP
502