Specifications
54 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
Note: Any CW flow rate of 3.0 GPM-5.0 GPM may have increased error in Flow Rate and Power Calculation. A Fluid Flow
Fault may result. Any flow rate under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)
6.6°C (12°F) 42.2 (144000) 42.2 (144000) 1.00 1.61 (25.5) 63.6 (21.3)
7.7°C (14°F) 41.0 (140000) 41.0 (140000) 1.00 1.38 (21.9) 46.3 (15.5)
8.8°C (16°F) 39.7 (136000) 39.7 (136000) 1.00 1.18 (18.7) 34.5 (11.6)
10°C (18°F)
38.3 (131000) 38.3 (131000) 1.00 1.01 (16.0) 25.8 (8.7)
11.1°C (20°F) 37.0 (126000) 37.0 (126000) 1.00 0.88 (14.0) 20.0 (6.7)
Temperature DB,
WB
°C (°F)
CW
Delta T
°C (°F)
Total Net Capacity Sensible Net Capacity
Sensible Heat
Ratio
CW
Flow Rate
Total CW
Pressure Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)