Specifications

52 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
Note: Any CW flow rate of 3.0 GPM-5.0 GPM may have increased error in Flow Rate and Power Calculation. A Fluid Flow
Fault may result. Any flow rate under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)
6.6°C (12°F) 40.4 (138000) 40.4 (138000) 1.00 1.58 (25.0) 59.2 (19.9)
7.7°C (14°F) 39.2 (134000) 39.2 (134000) 1.00 1.23 (19.5) 37.0 (12.4)
8.8°C (16°F) 37.8 (129000) 37.8 (129000) 1.00 1.13 (17.8) 31.5 (10.6)
10°C (18°F)
36.4 (124000) 36.4 (124000) 1.00 0.96 (15.2) 23.4 (7.9)
11.1°C (20°F) 34.9 (119000) 34.9 (119000) 1.00 0.83 (13.2) 18.05 (6.1)
48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)
6.6°C (12°F) 45.7 (156000) 45.7 (156000) 1.00 1.77 (28.0) 73.7 (24.7)
7.7°C (14°F) 44.7 (152000) 44.7 (152000) 1.00 1.36 (21.5) 44.5 (14.9)
8.8°C (16°F) 43.4 (148000) 43.4 (148000) 1.00 1.29 (20.4) 40.5 (13.6)
10°C (18°F)
42.1 (144000) 42.1 (144000) 1.00 1.10 (17.5) 30.4 (10.2)
11.1°C (20°F) 40.7 (139000) 40.7 (139000) 1.00 0.96 (15.3) 23.6 (7.9)
Temperature DB,
WB
°C (°F)
CW
Delta T
°C (°F)
Total Net Capacity Sensible Net Capacity
Sensible Heat
Ratio
CW
Flow Rate
Total CW
Pressure Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)