Specifications
50 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
Note: Any CW flow rate of 3.0 GPM-5.0 GPM may have increased error in Flow Rate and Power Calculation. A Fluid Flow
Fault may result. Any flow rate under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)
6.6°C (12°F) 45.3 (154000) 45.3 (154000) 1.00 1.77 (28.1) 73.8 (24.7)
7.7°C (14°F) 44.0 (150000) 44.0 (150000) 1.00 1.48 (23.5) 52.8 (17.7)
8.8°C (16°F) 42.5 (145000) 42.5 (145000) 1.00 1.25 (19.9) 38.6 (12.9)
10°C (18°F)
41.1 (140000) 41.1 (140000) 1.00 1.08 (17.1) 29.0 (9.7)
11.1°C (20°F) 39.7 (135000) 39.7 (135000) 1.00 1.04 (16.4) 27.0 (9.1)
48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)
7.7°C (14°F) 49.3 (168000) 49.3 (168000) 1.00 1.53 (24.2) 55.7 (18.7)
8.8°C (16°F) 48.1 (164000) 48.1 (164000) 1.00 1.42 (22.5) 48.6 (16.3)
10°C (18°F)
46.7 (159000) 46.7 (159000) 1.00 1.22 (19.4) 36.7 (12.3)
11.1°C (20°F) 45.4 (155000) 45.4 (155000) 1.00 1.07 (16.9) 28.6 (9.6)
Temperature DB,
WB
°C (°F)
CW
Delta T
°C (°F)
Total Net Capacity Sensible Net Capacity
Sensible
Heat Ratio
CW
Flow Rate
Total CW
Pressure Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)