Specifications
44 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
Note: Any CW flow rate of 3.0 GPM-5.0 GPM may have increased error in Flow Rate and Power Calculation. A Fluid Flow
Fault may result. Any flow rate under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
40.50°C DB, 20.8°C WB (105°F DB, 69°F WB)
6.6°C (12°F) 48.2 (164000) 48.2 (164000) 1.00 1.92 (30.4) 88.3 (29.6)
7.7°C (14°F) 46.7 (159000) 46.7 (159000) 1.00 1.57 (24.9) 58.7 (19.7)
8.8°C (16°F) 45.3 (155000) 45.3 (155000) 1.00 1.33 (21.1) 43.1 (14.5)
10°C (18°F)
43.8 (149000) 43.8 (149000) 1.00 1.14 (18.1) 32.4 (10.9)
11.1°C (20°F) 42.3 (144000) 42.3 (144000) 1.00 1.00 (15.8) 25.2 (8.4)
43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)
7.7°C (14°F) 52.4 (179000) 52.4 (179000) 1.00 1.76 (27.9) 73.0 (24.5)
8.8°C (16°F) 51.1 (174000) 51.1 (174000) 1.00 1.50 (23.8) 54.0 (18.1)
10°C (18°F)
49.6 (169000) 49.6 (169000) 1.00 1.29 (20.5) 40.9 (13.7)
11.1°C (20°F) 48.2 (164000) 48.2 (164000) 1.00 1.13 (17.9) 31.7 (10.6)
46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)
7.7°C (14°F) 57.9 (198000) 57.9 (198000) 1.00 1.94 (30.7) 87.7 (29.4)
8.8°C (16°F) 56.6 (193000) 56.6 (193000) 1.00 1.66 (26.3) 65.3 (21.9)
10°C (18°F)
55.2 (189000) 55.2 (189000) 1.00 1.44 (22.8) 49.7 (16.7)
11.1°C (20°F) 53.9 (184000) 53.9 (184000) 1.00 1.26 (19.9) 38.7 (13.0)
48.89°C DB, 23.3°C WB (120°F DB, 74°F WB)
8.8°C (16°F) 62.0 (212000) 62.0 (212000) 1.00 1.81 (28.7) 77.3 (25.9)
10°C (18°F)
60.7 (207000) 60.7 (207000) 1.00 1.57 (24.9) 59.0 (19.8)
11.1°C (20°F) 59.3 (202000) 59.3 (202000) 1.00 1.38 (21.9) 46.3 (15.5)
Temperature DB,
WB
°C (°F)
CW
Delta T
°C (°F)
Total Net Capacity Sensible Net Capacity
Sensible
Heat Ratio
CW
Flow Rate
Total CW
Pressure Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)