Specifications
42 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
Note: Any CW flow rate of 3.0 GPM-5.0 GPM may have increased error in Flow Rate and Power Calculation. A Fluid Flow
Fault may result. Any flow rate under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)
5.5°C (10°F) 28.3 (97000) 28.3 (97000) 1.00 1.28 (20.3) 80.5 (27.0)
6.6°C (12°F) 27.3 (93000) 27.3 (93000) 1.00 01.03 (16.4) 55.4 (18.6)
7.7°C (14°F) 26.0 (89000) 26.0 (89000) 1.00 0.84 (13.3) 38.6 (13.0)
8.8°C (16°F) 24.9 (85000) 24.9 (85000) 1.00 0.70 (11.2) 28.3 (9.5)
10°C (18°F)
23.8 (81000) 23.8 (81000) 1.00 0.60 (9.5) 21.1 (7.1)
11.1°C (20°F) 22.6 (77000) 22.6 (77000) 1.00 0.51 (8.1) 15.8 (5.3)
46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)
6.6°C (12°F) 30.7 (108000) 30.7 (108000) 1.00 1.16 (18.4) 67.7 (22.7)
7.7°C (14°F) 29.4 (100000) 29.4 (100000) 1.00 0.95 (15.0) 47.6 (16.0)
8.8°C (16°F) 28.3 (96000) 28.3 (96000) 1.00 0.80 (12.6) 35.3 (11.8)
10°C (18°F)
27.2 (93000) 27.2 (93000) 1.00 0.68 (10.8) 26.7 (9.0)
11.1°C (20°F) 26.0 (89000) 26.0 (89000) 1.00 0.59 (9.3) 20.4 (6.8)
48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)
6.6°C (12°F) 34.0 (116000 34.0 (116000 1.00 1.28 (20.3) 79.4 (26.6)
7.7°C (14°F) 32.8 (112000) 32.8 (112000) 1.00 1.05 (16.6) 57.0 (19.1)
8.8°C (16°F) 31.7 (108000) 31.7 (108000) 1.00 0.89 (14.1) 42.7 (14.3)
10°C (18°F)
30.5 (104000) 30.5 (104000) 1.00 0.76 (12.1) 32.6 (10.9)
11.1°C (20°F) 29.4 (104000) 29.4 (104000) 1.00 0.66 (10.5) 25.4 (8.5)
Temperature DB,
WB
°C (°F)
CW
Delta T
°C (°F)
Total Net Capacity Sensible Net Capacity
Sensible Heat
Ratio
CW
Flow Rate
Total CW
Pressure Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)