40 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
Note: Any CW flow rate of 3.0 GPM-5.0 GPM may have increased error in Flow Rate and Power Calculation. A Fluid Flow
Fault may result. Any flow rate under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)
6.6°C (12°F) 30.3 (103000) 30.3 (103000) 1.00 1.14 (18.0) 65.5 (22.0)
7.7°C (14°F) 28.9 (99000) 28.9 (99000) 1.00 0.93 (14.8) 46.3 (15.5)
8.8°C (16°F) 27.7 (94000) 27.7 (94000) 1.00 0.78 (12.4) 34.1 (11.4)
10°C (18°F)
26.5 (90000) 26.5 (90000) 1.00 0.66 (10.5) 25.5 (8.5)
11.1°C (20°F) 25.4 (87000) 25.4 (87000) 1.00 0.57 (9.1) 19.5 (6.5)
46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)
6.6°C (12°F) 33.7 (115000) 33.7 (115000) 1.00 1.26 (20.0) 78.8 (26.4)
7.7°C (14°F) 32.3 (110000) 32.3 (110000) 1.00 1.04 (16.5) 56.0 (18.8)
8.8°C (16°F) 31.1 (106000) 31.1 (106000) 1.00 0.88 (13.9) 41.5 (13.9)
10°C (18°F)
29.9 (102000) 29.9 (102000) 1.00 0.75 (11.8) 31.4 (10.5)
11.1°C (20°F) 28.8 (98000) 28.8 (98000) 1.00 0.65 (10.3) 24.3 (8.2)
48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)
7.7°C (14°F) 35.7 (122000) 35.7 (122000) 1.00 1.15 (18.1) 66.4 (22.2)
8.8°C (16°F) 34.5 (118000) 34.5 (118000) 1.00 0.97 (15.3) 49.3 (16.5)
10°C (18°F)
33.3 (114000) 33.3 (114000) 1.00 0.83 (13.1) 37.8 (12.7)
11.1°C (20°F) 32.2 (110000) 32.2 (110000) 1.00 0.72 (11.5) 29.7 (10.0)
Temperature DB,
WB
°C (°F)
CW
Delta T
°C (°F)
Total Net Capacity Sensible Net Capacity
Sensible
Heat Ratio
CW
Flow Rate
Total CW
Pressure Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)