Specifications
38 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
Note: Any CW flow rate of 3.0 GPM-5.0 GPM may have increased error in Flow Rate and Power Calculation. A Fluid Flow
Fault may result. Any flow rate under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)
6.6°C (12°F) 33.5 (114000) 33.5 (114000) 1.00 1.26 (20.0) 78.9 (38.7)
7.7°C (14°F) 32.3 (110000) 32.3 (110000) 1.00 1.04 (16.5) 56.0 (18.8)
8.8°C (16°F) 31.0 (106000) 31.0 (106000) 1.00 0.87 (13.8) 41.0 (13.8)
10°C (18°F)
29.7 (101000) 29.7 (101000) 1.00 0.74 (11.) 31.1 (10.4)
11.1°C (20°F) 28.6 (98000) 28.6 (98000) 1.00 0.64 (10.2) 24.0 (8.1)
46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)
7.7°C (14°F) 35.7 (122000) 35.7 (122000) 1.00 1.15 (18.2) 66.6 (22.3)
8.8°C (16°F) 34.4 (117000) 34.4 (117000) 1.00 0.96 (15.3) 49.0 (16.4)
10°C (18°F)
33.1 (113000) 33.1 (113000) 1.00 0.83 (13.1) 37.5 (12.6)
11.1°C (20°F) 32.0 (109000) 32.0 (109000) 1.00 0.72 (11.4) 29.2 (9.8)
48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)
7.7°C (14°F) 39.1 (134000) 39.1 (134000) 1.00 1.26 (19.9) 78.0 (26.2)
8.8°C (16°F) 37.8 (129000) 37.7 (129000) 1.00 1.06 (16.7) 57.6 (19.3)
10°C (18°F)
36.5 (125000) 36.5 (125000) 1.00 0.91 (14.4) 44.2 (14.8)
11.1°C (20°F) 35.4 (121000) 35.4 (121000) 1.00 0.79 (12.6) 35.0 (11.7)
Temperature DB,
WB
°C (°F)
CW
Delta T
°C (°F)
Total Net Capacity Sensible Net Capacity
Sensible
Heat Ratio
CW
Flow Rate
Total CW
Pressure Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)