Specifications

34 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
Note: Any CW flow rate of 3.0 GPM-5.0 GPM may have increased error in Flow Rate and Power Calculation. A Fluid Flow
Fault may result. Any flow rate under 3.0 GPM may also display as 0 in Flow Rate and Power Calculation.
43.33°C DB, 22.4°C WB (110°F DB, 72°F WB)
7.7°C (14°F) 35.8 (122000) 35.4 (121000) 0.99 1.15 (18.2) 66.9 (22.4)
8.8°C (16°F) 34.4 (117000) 34.0 (116000) 0.99 0.96 (15.3) 49.1 (16.5)
10°C (18°F)
33.1 (113000) 32.8 (112000) 0.99 0.82 (13.0) 37.1 (12.5)
11.1°C (20°F) 31.9 (109000) 31.6 (108000) 0.99 0.72 (11.4) 29.2 (9.8)
46.11°C DB, 23.3°C WB (115°F DB, 74°F WB)
7.7°C (14°F) 39.2 (134000) 38.8 (132000) 0.99 1.26 (20.0) 78.3 (26.3)
8.8°C (16°F) 37.8 (129000) 37.4 (128000) 0.99 1.06 (16.8) 57.7 (19.3)
10°C (18°F)
36.5 (124000) 36.1 (123000) 0.99 0.90 (14.3) 43.9 (14.7)
11.1°C (20°F) 35.3 (120000) 35.0 (119000) 0.99 0.79 (12.5) 34.8 (11.7)
48.89°C DB, 23.9°C WB (120°F DB, 75°F WB)
8.8°C (16°F) 41.2 (141000) 40.8 (140000) 0.99 1.15 (18.2) 66.8 (22.4)
10°C (18°F)
39.9 (136000) 39.5 (135000) 0.99 0.99 (15.7) 51.3 (17.2)
11.1°C (20°F) 38.8 (132000) 38.4 (131000) 0.99 0.87 (13.8) 40.9 (13.7)
Temperature DB,
WB
°C (°F)
CW
Delta T
°C (°F)
Total Net Capacity Sensible Net Capacity
Sensible
Heat Ratio
CW
Flow Rate
Total CW
Pressure Drop
kW (BTU/hr) kW (BTU/hr) SHR l/s (GPM) kPa (ft H2O)