Specifications
30 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
Recommended Capacity Limitations
ACRC301S
ACRC301H
ACRC500/ACRP500 series
IT Equipment IT Equipment Air Flow Recommended Capacity Limit
°C (°F) l/s per kW (CFM/kW) kW
5.56 (10) 150 (317) 10.1
8.33 (15) 100 (211) 15.1
11.11 (20) 75 (158) 20.3
13.89 (25) 60 (128) 25.0
16.67 (30) 50 (107) 30.0
19.44 (35) 43 (92) 34.7
22.22 (40) 38 (81) 39.7
25 (45) 34 (72) 44.7
IT Equipment IT Equipment Air Flow Recommended Capacity Limit
°C (°F) l/s per kW (CFM/kW) kW
5.56 (10) 150 (317) 13.3
8.33 (15) 100 (211) 19.9
11.11 (20) 75 (158) 26.5
13.89 (25) 60 (128) 32.9
16.67 (30) 50 (107) 39.4
19.44 (35) 43 (92) 45.6
22.22 (40) 38 (81) 52.1
25 (45) 34 (72) 58.6
IT Equipment IT Equipment Air Flow Recommended Capacity Limit
°C (°F) l/s per kW (CFM/kW) kW
11.0 (19.8) 75.5 (160) 43
11.3 (20.4) 73.2 (155) 45
11.7 (21.1) 70.8 (150) 46
12.1 (21.8) 68.4 (145) 48
12.5 (22.6) 66.1 (140) 49
13.0 (23.4) 63.7 (135) 51
13.5 (24.3) 61.4 (130) 53
14.1 (25.3) 59.0 (125) 55
14.6 (26.4) 56.6 (120) 58
15.3 (27.5) 54.3 (115) 60
15.9 (28.7) 51.9 (110) 63
16.7 (30.1) 49.6 (105) 66
17.5 (31.6) 47.2 (100) 69