Specifications

990-4618C-001 InRow Chilled Water Air Conditioners Technical Specifications 15
Alarms
The microprocessor controller shall activate a visible and audible alarm in the following occurrences:
Active Flow Controller sensor fault
Air filter clogged
Air filter run hours violation
Check condensate management system
Chilled water flow meter fault
Chilled water valve actuator fault
Chilled water valve control not set to automatic
Coil chilled water temperature sensor error
Coil condensation possible
Condensate pan full (excluding ACRC301H)
Controller power supply X fault
Cool fail
EcoAisle door open
Entering chilled water high temperature high violation
Entering/leaving chilled water temperature sensor fault
Factory configuration not completed
Fan X error
Fan power supply X current sense fault
Fan power supply X fault (ACRC301 series only)
Filter differential pressure sensor fault
Humidity sensor fault
Input contact fault
Insufficient airflow
Internal communication fault
Lower return air/supply air sensor fault
Primary/secondary power source fail
Rack high temperature condition
Rack temperature sensor X error
Return air/supply air high temperature violation
Shutdown due to input contact
Unexpected number of AFCs/leak detectors/rack inlet temperature sensors/units in group
Unit is in maintenance mode
Unit service required
Upper return air/supply air sensor fault
Water detected fault/shutdown