Specifications

10 InRow Chilled Water Air Conditioners Technical Specifications 990-4618C-001
Optional features
Cable water detector A leak detection cable for 300-mm units (NBES0308 and
NBES0309) or 600-mm units (AP9325 and AP9326) is placed on
the floor or sub-floor around all possible leak sources. If water or
other conductive liquids contact the cable anywhere along its
length, the microprocessor controller visually and audibly
announces a leak. The 6.1-m (20-ft) cable may be cascaded to
make custom lengths up to 24.4 m (80 ft).
Network cable Various lengths of network cable are available to ship with your
cooling system. The network cable is used to interconnect multiple
cooling units in a redundant group, as well as to connect the
network management card to your local area network (LAN).
Power trough Overhead power distribution between adjacent NetShelter racks
allows for removal of the InRow RC unit without disrupting
overhead power cabling.
Data partition Overhead cable distribution between adjacent NetShelter racks
allows for removal of the InRow RC unit without disrupting
overhead cabling.
Height adapters To match the height of the InRow RC unit to various rack heights,
height adapters are available for NetShelter 42-U VX, 45-U SX,
and 48-U SX racks.
Depth extender Used to match the depth of the InRow RC unit to deeper racks.
Rack Air Containment The Containment Solution isolates the airflow of individual racks
and InRow cooling units from the whole IT environment,
increasing efficiency while allowing for high density deployment.
Aisle Containment The Containment Solution isolates pods (two rows of racks sharing
a common aisle) from the whole IT environment, increasing
cooling efficiency at any density. For details, see “EcoAisle™
Aisle Containment System” on page 4.
Upper piping kit Available for top-piping configurations and can be field installed.
Note:Pre-installed in ACRC500 and ACRP500RP series units.
Dew point control pump
(ACRC301H only)
The condensate control pump allows the unit to recirculate coil
water to keep the unit operating above dew point.
Disposable pleated filter
(ACRC301S and ACRC301H only)
The filtration of conditioned air is extremely vital to maintaining
the clean, particle-free environment required by electrical
equipment. As an optional feature, the system uses a 50.8-mm (2-
in) pleated, deep-loading, 30% ASHRAE 52.1 filter (MERV 8 per
ASHRAE 52.2).