Specifications

38 InRow™ Direct Expansion Air Conditioners Technical Specifications 990-4617
Piping and Mechanical Connections
Refrigeration piping diagram (ACRD100/ACRD500/ACRP100 series))
Note: Shutoff valves shown nearest to the condensers are not supplied by APC by Schneider
Electric.
ACRD500/ACRP100 series: The shutoff valves nearest to the cooling unit are supplied by APC by
Schneider Electric.
ACRD100 series: The shutoff valves are not supplied and must be ordered.
Route piping through the top or bottom of the InRow ACRD/ACRP series.
All lines are Type L ACR copper tubing.
Trap the vertical discharge line every 6 m (20 ft) to ensure proper oil return.
Pipe size should change after the P-trap based on the recommended piping charts provided with
the installation manual.
For the ACRD500/ACRP100 series, the maximum piping run is 61 m (200 ft) equivalent length.
Size the piping pursuant to accepted refrigeration practice.
Fore the ACRD100 series, piping is 46m (150 ft) equivalent length. Size the piping pursuant to
accepted refrigeration practices.
Warning: Do not install the air-cooled condenser below the InRow ACRD/ACRP series. The
condenser must be positioned above or at the same level as the InRow ACRD/ACRP series to
ensure proper function.
Pitch in direction of refrigerant flow; 4 mm per m
(1/2 in per 10 ft)
P-trap
Shutoff valves S-trap
Head pressure control valve Inverted P-trap
Check valve Pressure relief valve
H
o
t
g
a
s
L
i
q
u
i
d
H
o
t
g
a
s
RD/RP
RD/RP
Receiver Receiver
Bottom piping
Top piping
Condenser Condenser
L
i
q
u
i
d