Specifications

34 InRow™ Direct Expansion Air Conditioners Technical Specifications 990-4617
Electrical Data
Note: Above data is based on maximum operating condition
Note: Installation must comply with national and/or local electrical codes.
Note: All models are hard-wired.
Note: Use LRA for estimation of inrush current.
* The compressor is powered by the VFD.
**Cells marked N/A indicate that this information is not required because of regional differences in electrical codes.
MCA—Minimum Circuit Amperes
MOP—Maximum Overcurrent Protection
FLA—Full Load Amps
LRA—Compressor Locked Rotor Amps
RLA—Compressor Rated Load Amps.
Model MCA** MOP** FLA**
Compressor
Power
LRA RLA
ACRD100 – 208-240V, 1 Ph, 60Hz 25 40 N/A 87.5 16.0 4.6
ACRD101 – 220-240V, 1 Ph, 50Hz N/A N/A 21 97.0 16.3 4.4
ACRD200 - 208-240V, 1 Ph, 60Hz 25 40 N/A 87.5 16.0 4.6
ACRD201 – 220-240V, 1 Ph, 50Hz N/A N/A 21 97.0 16.3 4.4
ACRD500 – 200-240V, 3 Ph, 50/60Hz 54.0 90 N/A 160* 50 15
ACRD501 – 460-480V, 3 Ph, 60Hz 27.0 40 N/A 139* 23.2 16
ACRD502 – 380-415V, 3 Ph, 50Hz N/A N/A 26.0 139* 23.2 16
ACRP100 – 200-240V, 3 Ph, 50/60Hz 80.1 100 N/A 160* 50 19
ACRP101 – 460-480V, 3 Ph, 60 Hz 39.9 50 N/A 139* 23.2 21
ACRP102– 380-415V, 3 Ph, 50/60Hz N/A N/A 32 139* 23.2 20