Specifications
990-4617 InRow™ Direct Expansion Air Conditioners Technical Specifications 25
*Airflow reduced to 4000 SCFM at this condition to maintain adequate return gas temperature.
Airflow at full evaporating fan speed: ACRD100/200 series – 1081 l/s (2290 SCFM); ACRD500/ACRP100 series – 2171 l/s (4600 SCFM).
Minimum recommended loads: ACRD100/200 series – 2kW (6,831 BTU); ACRD500/ACRP100 series – 10kW (34,152 BTU)
Note: For ACRD100, ACRD500, and ACRP100 series the outdoor air temperature is 35°C (95°F)
Note: For ACRD200 series, a 40% at 0.64 l/s (10gpm), the entering glycol mixture temperature is 40.6°C (105°F)
Note: For ACRD500 series, reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380V).
Net Cooling Capacity (Water Cooled)
Airflow for the ACRD200 series is 1081 l/s (2290 SCFM) at full evaporating fan speed.
Note: Minimum recommended loads: ACRD200 series - 2kW (6,831 BTU)
Note: For ACRD200 series, a 0.64 l/s (10gpm) entering water temperature is 29.4°C (85°F)
43.3°C DB, 22.2°C WB) (110°F DB, 72.0°F WB
5
Airflow is reduced to 448 l/s (950 SCFM) at this
condition to maintain adequate evaporating
temperature.
ACRD100
5
10.6 (36,000) 10.6 (36,000)
ACRD101
5
10.5 (35,900) 10.5 (35,900)
ACRD200
5
10.6 (36,000) 10.6 (36,000)
ACRD201
5
10.5 (35,900) 10.5 (35,900)
Return Air Temperature Model Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr)
22.2°C DB, 15.5°C WB (72°F DB, 60°F WB)
ACRD200 9.72 (33,200) 8.94 (30,500)
ACRD201 9.57 (32,700) 8.79 (30,100)
23.9°C DB, 16.2°C WB (75°F DB, 61.1°F WB)
ACRD200 8.43 (32,200) 8.43 (32,200)
ACRD201 9.30 (31,800) 9.30 (31,800)
26.7°C DB, 19.4°C WB (80°F DB, 67.0°F WB)
ACRD200 11.52 (39,300) 9.90 (33,800)
ACRD201 11.64 (39,800) 9.99 (34,200)
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
ACRD200 10.38 (35,400) 10.38 (35,400)
ACRD201 10.11 (34,500) 10.11 (34,500)
29.4°C DB, 18.1°C WB (85°F DB, 64.6°F WB)
ACRD200 10.92 (37,300) 10.92 (37,300)
ACRD201 10.98 (37,500) 10.98 (37,500)
32.2°C DB, 19.0°C WB (90°F DB, 66.2°F WB)
Note: Airflow is reduced to 887 l/s (1880 SCFM) at this
condition to maintain adequate evaporating temperature.
ACRD200 11.64 (39,700) 11.64 (39,700)
ACRD201 11.76 (40,200) 11.76 (40,200)
35.0°C DB, 19.9°C WB (95°F DB, 67.8°F WB)
Note: Airflow is reduced to 717 l/s (1520 SCFM) at this
condition to maintain adequate evaporating temperature.
ACRD200 12.00 (41,000) 12.00 (40,900)
ACRD201 12.00 (41,000) 12.00 (41,000)
37.8°C DB, 20.7°C WB (100°F DB, 69.3°F WB)
Note: Airflow is reduced to 599 l/s (1270 SCFM) at this
condition to maintain adequate evaporating temperature.
ACRD200 12.06 (41,200) 12.06 (41,200)
ACRD201 12.00 (41,000) 12.00 (41,000)
40.6°C DB, 21.6°C WB) (105°F DB, 70.8°F WB
Note: Airflow is reduced to 510 l/s (1080 SCFM) at this
condition to maintain adequate evaporating temperature.
ACRD200 12.06 (41,000) 12.00 (41,000)
ACRD201 12.00 (41,000) 12.00 (41,000)
43.3°C DB, 22.2°C WB) (110°F DB, 72.0°F WB
Note: Airflow is reduced to 448 l/s (950 SCFM) at this
condition to maintain adequate evaporating temperature.
ACRD200 12.06 (41,200) 12.06 (41,200)
ACRD201 12.06 (41,200) 12.06 (41,200)
Return Air Temperature Model Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr)