Specifications

24 InRow™ Direct Expansion Air Conditioners Technical Specifications 990-4617
Performance Specifications
Net cooling capacity (air and glycol cooled)
Return Air Temperature Model Total Capacity kW (BTU/hr) Sensible Capacity kW (BTU/hr)
22.2°C DB, 15.5°C WB (72°F DB, 60°F WB)
ACRD100 8.22 (28,000) 8.04 (27,400)
ACRD101 8.01 (27,200) 7.71 (26,400)
ACRD200 8.22 (28,000) 8.04 (27,400)
ACRD201 8.01 (27,200) 7.71 (26,400)
ACRD500/ACRP100 series 22.8 (78,000) 19.0 (65,000)
23.9°C DB, 16.2°C WB (75°F DB, 61.1°F WB)
ACRD100 8.52 (29,000) 8.52 (29,000)
ACRD101 8.16 (27,900) 8.16 (27,900)
ACRD200 8.52 (29,000) 8.52 (29,000)
ACRD201 8.16 (27,900) 8.16 (27,900)
ACRD500/ACRP100 series 25.2 (86,000) 21.7 (74,000)
26.7°C DB, 19.4°C WB (80°F DB, 67.0°F WB)
ACRD100 10.02 (34,000) 9.12 (31,000)
ACRD101 9.72 (33,200) 8.85 (30,200)
ACRD200 10.02 (34,000) 9.12 (31,000)
ACRD201 9.72 (33,200) 8.85 (30,200)
ACRD500/ACRP100 series
N/A N/A
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
ACRD100 9.36 (32,000) 9.36 (32,000)
ACRD101 8.97 (30,700) 8.97 (30,700)
ACRD200 10.02 (34,000) 9.12 (31,000)
ACRD201 9.72 (33,200) 8.85 (30,200)
ACRD500/ACRP100 series 26.9 (92,000) 26.9 (92,000)
29.4°C DB, 18.1°C WB (85°F DB, 64.6°F WB)
ACRD100 9.90 (33,800) 9.90 (33,800)
ACRD101 9.69 (33,100) 9.69 (33,100)
ACRD200 9.90 (33,800) 9.90 (33,800)
ACRD201 9.69 (33,100) 9.69 (33,100)
ACRD500/ACRP100 series 29.0 (99,000) 29.0 (99,000)
32.2°C DB, 19.0°C WB (90°F DB, 66.2°F WB)
1
Airflow is reduced to 887 l/s (1880 SCFM) at this
condition to maintain adequate evaporating
temperature.
ACRD100
1
10.44 (35,600) 10.44 (35,600)
ACRD101
1
10.29 (35,200) 10.29 (35,200)
ACRD200
1
10.44 (35,600) 10.44 (35,600)
ACRD201
1
10.29 (35,200) 10.29 (35,200)
ACRD500/ACRP100 series 30.5 (104,000) 30.5 (104,000)
35.0°C DB, 19.9°C WB (95°F DB, 67.8°F WB)
2
Airflow is reduced to 717 l/s (1520 SCFM) at this
condition to maintain adequate evaporating
temperature
ACRD100
2
10.62 (36,200) 10.62 (36,200)
ACRD101
2
10.5 (35,900) 10.5 (35,900)
ACRD200
2
10.62 (36,200) 10.62 (36,200)
ACRD201
2
10.5 (35,900) 10.5 (35,900)
ACRD500/ACRP100 series 33.7 (115,000) 33.7 (115,000)
37.8°C DB, 20.7°C WB (100°F DB, 69.3°F WB)
3
Airflow is reduced to 599 l/s (1270 SCFM) at this
condition to maintain adequate evaporating
temperature.
ACRD100
3
10.62 (36,200) 10.62 (36,200)
ACRD101
3
10.5 (35,900) 10.5 (35,900)
ACRD200
3
10.62 (36,200) 10.62 (36,200)
ACRD201
3
10.5 (35,900) 10.5 (35,900)
ACRD500/ACRP100 series 36.9 (126,000) 36.9 (126,000)
40.6°C DB, 21.6°C WB) (105°F DB, 70.8°F WB
4
Airflow is reduced to 510 l/s (1080 SCFM) at this
condition to maintain adequate evaporating
temperature
ACRD100
4
10.56 (36,000) 10.56 (36,000)
ACRD101
4
10.5 (35,900) 10.5 (35,900)
ACRD200
4
10.56 (36,000) 10.56 (36,000)
ACRD201
4
10.5 (35,900) 10.5 (35,900)
ACRD500/ACRP100 series* 36.6 (125,000) 36.6 (125,000)