Specifications

990-4617 InRow™ Direct Expansion Air Conditioners Technical Specifications 11
Control
The backlit, four-line by twenty-character display is password configurable.
Alarms
The microprocessor controller shall activate a visible and audible alarm in the following occurrences:
All series:
• Cool Fail
Air filter clogged
Return air sensor fault
Supply air sensor fault
Rack temperature sensor fault
High discharge pressure
Low suction pressure
• Fan fault
Water detected (if optional leak detector used)
Check condensate management system
Air filter run hours violation
Group communication fault
Supply air high temperature violation
Return air high temperature violation
Filter DP sensor failure
Suction pressure sensor failure
Discharge pressure sensor failure
Persistent high discharge pressure fault
Rack inlet temperature high violation
External communication fault
Internal communication fault
On standby input contact fault
A-link isolation relay fault
ACRD100 series and ACRD200 series only:
Condensate pan full
Upper fan power supply fault
Lower fan power supply fault
Suction temperature sensor failure
Persistent low suction pressure fault
Factory configuration not completed
Liquid refrigerant sensor failure