Specifications

8 InRow™ Direct Expansion Air Conditioners Technical Specifications 990-4617
Optional Features
Cable water detector
A leak detection cable is placed on the floor or subfloor around all possible leak sources. If water or other
conductive liquids contact the cable anywhere along its length, the microprocessor controller announces the
leak visually, audibly, and across the network. The 6.1-m (20-ft) cable may be cascaded to make custom
lengths up to 24.4 m (80-ft).
Network cable
Various lengths of network cable are available to ship with your cooling system. The network cable is used to
interconnect multiple cooling units in a redundant group, as well as to connect the Network Management Card
to your LAN.
Filters
Electrical equipment requires clean, particle free air, thus making air filtration extremely important. As an
optional feature, higher efficiency filters can be purchased for the InRow DX units. The ACRD100 and
ACRD200 series units optionally use an 50.8 mm (2 in) pleated, deep loading, 30% ASHRAE 52.1 filter
(MERV 8 per ASHRAE 52.2). The ACRD500 and ACRP100 series units optionally use 102 mm (4 in) pleated,
deep loading, 85% ASHRAE 52.1 filter (MERV13 per ASHRAE 52.2).
Power Trough
Overhead power distribution between adjacent NetShelter racks allows for removal of the InRow DX without
disrupting overhead power cabling.
Data Partition
Overhead cable distribution between adjacent NetShelter racks allows for removal of the InRow RP without
disrupting overhead cabling.
Height Adapters
To match height of the InRow RP to various rack heights, height adapters are available for NetShelter 42U VX
and 48U SX racks.