Water Dispenser User Manual
5InRow RP Technical Data Manual
Dual Position Float 
Condensate Management
The pump is factory wired and piped 
internally to the condensate drain pan 
and humidifier outlet. The pump is 
capable of pumping a maximum of 
18 m (60 ft) at 0.009 l/s (8.45 GPH), 
which may include a maximum lift of 
3.5 m (11.5 ft) of head. A dual 
position float is included with the 
unit. One position is used for 
condensate pump control, the other to 
alarm condensate pump failure which 
shuts down the RP to prevent 
condensate pump overflow.
Network Management Card
Permits multi-level access to 
monitoring, control, and event 
notification features over the user’s 
network.
Bay Kit InRow RP/
NetShelter SX
Baying kits made of 1.5 mm 
(16 gauge) steel enable baying of the 
cooling system to APC NetShelter 
SX enclosures.
Remote Temperature 
Sensors
To control the unit based on rack inlet 
temperature, three remote sensors are 
provided. These sensors measure at 
4 m (13 ft) from the connection point 
inside the RP. The sensors are used 
for remote placement in the field on 
adjacent IT racks.
Humidifier
The humidifier is a self-contained, 
steam-generating type, factory piped 
and wired, with a disposable cylinder 
and an automatic solid state control 
circuit. Humidifier canisters are 
replaceable. The humidifier 
controller communicates directly to 
the microprocessor controller and 
provides complete status and control 
at the operator interface.