Specifications
Specifications
66 40kW InfraStruXure PDU—Operation and Configuration
Cable Connections IEC 309, 16A
Cable Lengths Various, determined by CTO
Power Cable Wiring—top Accommodates 28, 3-phase power cables (42 knock-outs)
Power Cable Wiring—bottom Accommodates 28, 3-phase power cables (48 knock-outs)
Panel Boards
Panel Style 3-phase
Number of Panels (per PDU) 2 maximum
Positions per Panel 42, double row
Breakers per Panel 42
1-phase breakers per panel 42 maximum
Panel rating 240V/ 225A per phase
Breaker Pitch 19mm
Accessibility Through front of unit
Over-current Protection
Main Input Breaker 125A
UPS Input Breaker 125A
Maintenance Breaker 100A
UPS Output Breaker 100A
Distribution Breakers 1-pole or 3-pole with or without ELCB, 10A, 16A, and 32A
Relay Outputs
Nominal Switching Capacity 1A at 30VDC
Maximum Switching Power 30W
Maximum Switching Voltage 60VDC
Maximum Switching Current 2ADC
Maximum Carrying Current 2ADC
Surge Ratings 2kV per Bellcore TA-NWT-001089
1.5kV per FCC part 68
Physical
Dimensions (H×W×D)
PDU 2070 × 597 × 902 mm (81 × 24 × 36in)
Shipping 2184 × 914 × 1219 mm (86 × 36 × 48in)
Shielding Trough 191 × 579 × 323 mm (7.5 × 23 × 13in)
Weight
PDU with Transformer 844kg (1861lb)
PDU without Transformer 590kg (1301lb)
Shipping with Transformer 867kg (1911lb)
Shipping without Transformer 613kg (1351lb)
Electrical