Specifications

System Operation
34 40kW InfraStruXure PDU—Operation and Configuration
c. Select UPS Into Bypass on the Control menu, and
press the
E
NTER
key.
Control Menu
d. Confirm the selection on the next screen: select Yes,
UPS into Bypass, and press the
E
NTER
key.
Confirmation Screen
Note
The H2 LED above the Q2 breaker illuminates, indicating that it is safe to
operate the Q2 breaker.
6. Close (turn ON) the Q2 breaker on the PDU.
Note
The H3 LED above the Q3 breaker illuminates, indicating that it is safe to operate
the Q3 breaker
7. Open (turn OFF) the Q3 breaker on the PDU.
The UPS automatically comes out of Static Bypass
operation.
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirm
Yes, UPS into Bypass
No, Abort