Specifications
System Operation
30 40kW InfraStruXure PDU—Operation and Configuration
The UPS BYPASS LED illuminates and the following screens appear:
Note
The H3 LED above the Q3 breaker illuminates, indicating that it is safe to operate
the Q3 breaker.
2. Close (turn ON) the Q3 breaker on the PDU.
Note
The H2 LED above the Q2 breaker illuminates, indicating that it is safe to operate
the Q2 breaker.
3. Open (turn OFF) the Q2 breaker on the PDU.
The UPS will show a Forced Bypass message on the
display interface, and the Fault LED will be red.
UPS has been
commanded to go
into Bypass...
UPS load is in Bypass
Press any key...