Specifications

40kW InfraStruXure PDU—Operation and Configuration 11
PDU Display Interface
Overview
You can use the display interface to configure settings, set alarm thresholds, and provide audible and
visual alarms.
ESC
?
Load
Powered
Check
Log
Bypass
Alarm

Load Powered
LED
When green, all output phases are within the limits specified by
the output alarm limit thresholds.
Check Log LED When yellow, at least one new alarm condition has been detected.
Bypass LED When yellow, power to the load is being supplied directly by the
utility power sourcethe UPS has been removed from the circuit
for maintenance or replacement. Bypass breakers on the PDU
function as input circuit breakers to protect the load equipment.
Alarm LED When red, an alarm condition exists.
LCD View alarms, status data, instructional help, and configuration
items.
Up and Down
navigation keys
Selects menu items and accesses information.
ENTER key Opens menu items and inputs changes to system parameters.
HELP key Launches context-sensitive help. Press the
HELP key for
information about each item on the screen and for instructions on
how to perform certain tasks (i.e. placing the UPS into
Maintenance Bypass operation.)
ESC key Returns to previous screen displayed.