Specifications
Overview
40kW InfraStruXure PDU—Operation and Configuration 9
User connection plate
For a description and location of the user connection plate, see (
) on page 6. For clarity, refer to the
following illustration which shows the user connection plate in greater detail.
Connect the InfraStruXure PDU to the network or the InfraStruXure Manager through the
ethernet port.
The user connection plate has four input contact connections for monitoring Normally
Open (NO) or Normally Closed (NC) dry contacts. See page 58 for more information.
The user connection plate has four relay output connections for connection of Normally
Open (NO) or Normally Closed (NC) dry contacts. See page 58 for more information.
Connect an Emergency Power Off (EPO) switch at one of the three choices of EPO
connections (24VDC, 24VAC, or contact closure). See page 59 for more information.
1 234
ATS EN
ATS 0
AT S 1
ATS 2
EPO
Contact
–
+
EPO 24V
AC/DC
Contact Inputs
Contact Output s
USER INTERFACE
© 2001 APC
MADE IN USA
!
!
!