Specifications

Overview
6 40kW InfraStruXure PDU—Operation and Configuration
Front view (interior)
The 42-position circuit breaker panels provide 84 total single pole positions. Each
single pole provides power at 230 volts L-N. The amperage each position provides
depends on the size of the circuit breaker used.
The document pocket provides storage of documents relating to the circuit breaker
panels, such as the PDU Panel Board Schedules (provided).
The wraparound maintenance bypass panel holds three circuit breakers that allow
the UPS to be electrically isolated from the mains, while maintaining the power
panels. The input circuit breaker is labeled Q1, the output circuit breaker is labeled
Q2, and the maintenance bypass circuit breaker is labeled Q3. The label on the
maintenance bypass panel of the PDU illustrates the power flow, and the H2 and H3
LEDs indicate when it is safe to operate the Q2 and Q3 circuit breakers.
The user connection plate is connected to the PDU monitoring unit, and provides
easy access to input contact, relay output, network, and EPO connections. Make
connections from inside the enclosure, and route wires through the knockout provided
on the plate.
!
!
!