Technical data
9 APC InRow SC Technical Data Manual
Air-cooled Performance Specifications
Note: Room condition 72
o
F db/50% RH.
Density ratio is used for air flow correction factor. Capacity correction is used for performance derate
NET COOLING CAPACITY
Model ACSC100 ACSC101
ELECTRICAL INPUT 200-240V, 1ph, 60Hz 200-240V, 1ph, 50Hz
70°F DB, 58.5°F WB (21.1°C DB, 14.7°C WB)
Total - BTU/hr (Watts)
16300 (4770) 15100 (4410)
Sensible - BTU/hr (Watts)
15100 (4440) 14300 (4200)
72°F DB, 60.0°F WB (22.2°C DB, 15.6°C WB)
Total - BTU/hr (Watts)
17000 (4980) 15400 (4510)
Sensible - BTU/hr (Watts)
15500 (4530) 14400 (4230)
75°F DB, 61.0°F WB (23.9°C DB, 16.1°C WB)
Total - BTU/hr (Watts)
16700 (4890) 16200 (4740)
Sensible - BTU/hr (Watts)
16200 (4740) 15900 (4650)
80°F DB, 67.0°F WB (26.7°C DB, 19.4°C WB)
Total - BTU/hr (Watts)
18100 (5310) 18000 (5250)
Sensible - BTU/hr (Watts)
15500 (4560) 16000 (4680)
80°F DB, 62.5°F WB (26.7°C DB, 16.9°C WB)
Total - BTU/hr (Watts)
17200 (5040) 16700 (4890)
Sensible - BTU/hr (Watts)
17200 (5040) 16700 (4890)
85°F DB, 65.0°F WB (29.4°C DB, 18.3°C WB)*
Total - BTU/hr (Watts)
18000 (5250) 16700 (4890)
Sensible - BTU/hr (Watts)
18000 (5250) 16700 (4890)
95°F DB, 82.7°F WB (35.0°C DB, 28.2°C WB)**
Total - BTU/hr (Watts)
22000 (6450) 21300 (6240)
Sensible - BTU/hr (Watts)
11300 (3300) 11300 (3300)
96°F DB, 68°F WB (35.5°C DB, 20°C WB)***
Total - BTU/hr (Watts)
22200 (6500) 19800 (5800)
Sensible - BTU/hr (Watts)
22200 (6500) 19800 (5800)
Note: All values are accurate to +/- 5% and based on full fan speed with standard filters and 95
o
F (35
o
C) Condenser entering air
All tests were performed at 100% evaporator fan speed except as noted. Net cooling data is published above.
*Airflow reduced to 1000 CFM (1700 m
3
/hr) at this condition to maintain appropriate suction temperature
**Airflow reduced to 600 CFM (1020 m
3
/hr) at this condition to maintain appropriate suction temperature
***Airflow reduced to 850 CFM (1440 m
3
/hr) to maintain appropriate suction temperature. Represents conditions with front and
rear containment
Altitude Correction Factors for InRow Products
Altitude (ft) 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Specific
Vo l u m e
13.58 14.09 14.62 15.18 15.76 16.36 17.00 17.67 18.37 19.11 19.89
Density lb/ft
3
0.074 0.071 0.068 0.066 0.063 0.061 0.059 0.057 0.054 0.052 0.050
Density Ratio 1.000 0.964 0.929 0.895 0.862 0.830 0.799 0.769 0.739 0.711 0.683
Capacity
Correction
1.00 0.981 0.962 0.933 0.913 0.884 0.865 0.846 0.826 0.807 0.787