Installation manual
General characteristics of MGE™ Galaxy™ 7000 UPSs >
34020846EN/AE - Page 64
2. Appendices
2.4 General characteristics of MGE™ Galaxy™ 7000 UPSs
UPS power in kVA 160 200 250 300 400 500
Normal AC input
Number of conductors 3 phases
Reference voltage at Pn 380 V to 415 V
Reference frequency 45 Hz to 66 Hz
THDI Typically 3% at Pn
Power factor > 0,99
Bypass AC input
Number of conductors 3 phases + neutral
Reference voltage at Pn 380 V to 415 V
Reference frequency 45 Hz to 66 Hz
Load output
Number of conductors 3 phases + neutral
Set phase-to-phase voltages 380 V / 400 V / 415 V
Set phase-to-neutral voltages 220 V / 230 V / 240 V
Voltage variation ± 1%
Adjustable frequencies and tolerance
(on battery power)
50 Hz or 60 Hz ± 0.1 Hz
Voltage variation for 0 to 100% load
step impact
± 1%
Permissible overloads 150% for 30 seconds, 125% for 10 minutes
THDU Ph-to-Ph and Ph-to-N for non-
linear load
< 2% Ph-to-Ph
Battery
Standard battery technology Sealed lead-acid battery (gas-recombination)
(Valve Regulated Lead Acid type)
UPS power in kVA 160 200 250 300 400 500
PN/2 PN PN/2 PN PN/2 PN PN/2 PN PN/2 PN PN/2 PN
Active power (kW)
72 144 90 180 112 225 135 270 180 360 225 450
Efficiency
92,0 93,2 93,0 93,0 93,2, 93,8 93,5 93,6 94,1 94,1 94,3 94,3
Heat losses in kW
Heat losses in calories/s
6,3
1496
10,5
2511
6,8
1619
13,5
3238
8,2
1962
14,9
3554
9,4
2243
18,6
4449
11,3
2697
22,6
5395
13,6
3250
27,2
6501
Storage temperature range -25°C to +45°C
Operating temperature range at Pn 0°C to 35°C
Relative humidity 45% to 75%
Maximum operating altitude without
derating
<1000 m
Noise level (dBa) 75
Product standards IEC 62040
Safety standards IEC 62040-1-2
Protection standards IEC 62040-3
EMC standards IEC 62040-2