Installation manual

Assembling and connecting the external battery cabinet >
34020846EN/AE - Page 57
1. Installation
Connecting the power cables
4 - Connect the control-wire cables, (
See “Connecting the control-wire
cables”, page 58.)
5 - Secure the protective cover after
connecting the batteries to the circuit
breaker.
This operation must be carried out by qualified personnel.
The door must be open
The protective cover must be removed.
The battery circuit breaker must be open.
Key:
(1) To the UPS cabinet
(2) To the battery or auxiliary battery
cabinet 2
1 - Connect the earthing conductor to
the earthing bar in the battery cabinet
(1)
2 - Connect the positive conductor (+)
to the positive terminal
3 - Connect the negative conductor
(+) to the negative terminal
4 - Secure the protective cover after
connecting the batteries to the circuit
breaker.
For more information, see the "Battery circuit-breaker kit" installation manual no. 34021530.
+
-
1 2
B +
B-