Installation manual

Assembling and connecting the external battery cabinet >
34020846EN/AE - Page 56
1. Installation
1.12 Assembling and connecting the external battery cabinet
Assembling the empty battery cabinet
Mounting the battery circuit-breaker kit
Mounting the shelves
Please contact our Sales department when selecting the battery circuit breaker.
Only one circuit breaker is necessary even if there are several battery cabinets.
1 - Secure the plate
2 - Secure connector XR1
3 - Secure the temperature sensor.
Assembly of the battery cabinet must be carried out by certified personnel (standard EN 50091-1-2).
The minimum clearance between the top of the battery cells and the next shelf is 150 mm.
1 - Secure the corner supports (6 screws per
support).
2 - Install the shelf
3 - Secure the shelf with two screws in each
corner.
2
1
1
1
3
3