Installation manual

Connecting the control-wire cables > Connecting the UPS units in parallel > Connect the components specific to the 2000 kVA light SSC
34020846EN/AE - Page 51
1. Installation
Connecting customer switches
For the installation to operate properly, the following must be respected:
Customer switches Q4S ext, Q3BP ext and Q5N ext must be electrically wired to behave like those of a SSC cabinet that
contains switches.
The auxiliary contact of a customer switch must be a normally open contact when the switch is open.
Wire size:
0.5 to 1.5 mm² / AWG20 to AWG16
1 - Connect XM4 to switches Q5N ext,
Q4S ext, Q3BP ext.
XM7
XM4
Q3BP ext
Q5N ext
1
4
Q4S ext
2000 light SSC cabinet