Installation manual

Layout >
34020846EN/AE - Page 13
1. Installation
Floor mounting
Normal or false floor.
UPS cabinets
SSC
800 and 1200 kVA
2000 kVA
Dimensions are indicated in millimetres.
The four feet (6 feet for 500 kVA UPS) of the
cabinet are cylindrical, 60 mm in diameter.
The measurements opposite include the
cabinet cover panels and the door.
Max. load on floor per square cm for the feet:
UPS cabinet
in kVA
Kg/cm2
160 9
200 9
250 11
300 11
400 13
500 11
Max. load on floor per square cm for the feet:
SSCs in kVA Kg/cm2
800 5
1200 9
2000 9
2000 light 7
64.5
27.5
290
849
160 - 400 kVA : 1357
500 kVA : 1757
250/300/400 kVA : 760
500 kVA : 1280
757
Cable-running
zone
Front
Top view
64.5
27.5
849
800 kVA : 957
1200 kVA : 1357
800 kVA : 1012 x 260
1200 kVA : 1280 x 260
757
Front
Cable-running zone
Top view
415 385
415
2452
415
870
64.5
27.5
757
849
957
1357
83
Cable-running zone
Top view
Cable-running
zone
Cable-running
zone
Front