Owners manual
91Rack Power Filter: How to Export Configuration Settings
The Upload Event and Error Messages
The event and its error messages
The following event occurs when the receiving Rack Power Filter completes using the .ini file to update
its settings.
Configuration file upload complete, with number valid values
If a keyword, section name, or value is invalid, the upload by the receiving Rack Power Filter succeeds,
and additional event text states the error.
Messages in config.ini
A Rack Power Filter from which you download the config.ini file must be discovered successfully in
order for its configuration to be included. If the Rack Power Filter is not present or is not discovered, the
config.ini file contains a message under the appropriate section name, instead of keywords and values.
For example:
Rack Power Filter not discovered
If you did not intend to export the configuration of the Rack Power Filter as part of the .ini file import,
ignore these messages.
Errors generated by overridden values
The Override keyword and its value will generate error messages in the event log when it blocks the
exporting of values.
Event text Description
Configuration file warning: Invalid
keyword on line number.
Configuration file warning: Invalid value
on line number.
A line with an invalid keyword or value is ignored.
Configuration file warning: Invalid
section on line number.
If a section name is invalid, all keyword/value pairs in that section
are ignored.
Configuration file warning: Keyword
found outside of a section on line number.
A keyword entered at the beginning of the file (i.e., before any
section headings) is ignored.
Configuration file warning:
Configuration file exceeds maximum
size.
If the file is too large, an incomplete upload occurs. Reduce the
size of the file, or divide it into two files, and try uploading again.