Owners manual
47Rack Power Filter:
Steps to Configure Auto-Reboot Setting
1. From the Configuration and Control tab, select Configuration and outlets.
2. Click the link on the outlet name, and then navigate to the outlet configuration parameters at the
bottom of the page.
3. Enter values for Target Host IP Address, Interval Between Successful Pings, Interval Between
Failed Pings, Failed Pings Before Reboot, Ping Delay After Reboot, Max Reboot Attempts , and
Check/Uncheck the check box for Auto-Reboot, Enable to retry after 24 hours.
4. Click the Apply button.
View the ProAV and Contact information
Path: Configuration and Control > About
The page shows the ProAV device information including device model name, device serial number,
device PIC firmware revision, device rating current and device manufacture date
This page also shows the contact information including company name, contact name, website, and
phone.
Unsuccessful Ping
Period
When a ping request fails (that is, it gets no response from a device), it may be
desirable to begin pinging at a shorter time interval. This enables the ProAV to more
quickly determine that the device is not functioning.
After each unsuccessful ping, ProAV will wait this time interval (in seconds) before
the next ping attempt. This time can be set from 1 to 60000 seconds (1000 minutes or
16.666 hours). The factory default for this setting is 10 seconds
Delay Before First
Ping After Reboot
When ProAV is first turned on, it will wait this time interval (in seconds) before
beginning to ping the device. This time delay allows the device to boot before being
pinged. This time can be set from 0 to 60000 seconds (1000 minutes or 16.666 hours).
The factory default for this setting is 120 seconds.
Failed Ping Before
Reboot
The device will re-boot after this number of ping failures. This number can range
from 1 to 255. The factory default for this setting is 5.
Max. Reboot
Attempts
After the device has been re-booted this number of times without any successful
pings, it is assumed that there are problems with the device and ProAV will no longer
attempt to re-boot the device.
Setting Descriptions