Owners manual

SwitchedRack Power Filter: Command Line Interface32
Protection Working: Good
olAutoRbt
Access: Administrator, Device User
Description: Set or view the auto-reboot setting for one or more outlets.
Example 1: Enable the auto-reboot function for outlet 3.
apc> olAutoRbt 3 -c enable -t www.apc.com
E000: Success
olCancelCmd
Access: Administrator, Device User
Description: Cancel a pending command for any outlet.
Example 1: Cancel a pending command for outlet 3.
apc> olCancelCmd3
E000: Success
olCtrlType
Access: Administrator, Device User
Description: View or set the control mode of an outlet.
Example 1: View the control mode of outlets 3, 5, 6, and 7.
apc> olCtrlType 3,5-7
E000: Success
Outlet 3: Master
Outlet 5: Controlled by Master
Outlet 6: Controlled by Master
Outlet 7: Controlled manually
Example 2. Set the control mode of outlet 3 to Reboot Only.
apc> olCtrlType 3 RebootOnly
Option Argument Description
-c <Enable/Disable> Enable or disable Auto-Rebooting feature
-r <Enable/Disable> Enable or disable Retry after 24 hours option
-t <Target host ip address> Format must be xxx.xxx.xxx.xxx
-s <Interval between successful ping> [ 1 – 6000 ]
-u < Interval between failed ping> [ 1 – 6000 ]
-f <Failed pings before reboot> [ 1 – 255 ]
-d <Ping Delay after reboot> [ 0 – 6000]
-m <Max retry attempts> [ 1 - 255 ]