IMPORTANTSAFETYINSTRUCTIONS
SAVETHESEINSTRUCTIONS
Thismanualcontainsimportantinstructionsthatshouldbefollowedduringinstallation,operation,and
maintenanceoftheEPOsystem.
SafetyInstructionsforNorthAmerica
WARNING:Onlycertiedelectriciansmayinstallthesystemandthewiringtothe
productsITcontrols.
WARNING:Assemblyhasnotbeenevaluatedforemergencylifecriticalapplications,
butisintendedforemergencyequipmentpoweroff.
Note:WiringfromthesystemtotheproductsITcontrolscaneitherbeinstalledinconduits
orinstalledwithoutconduitsifthewiresareinaccordancewithArticle725oftheNational
ElectricalCode(NFPA70)andSection16oftheCanadianElectricalCode(C22.1).
Caution:OnlyClass2circuitsrated30Vorlesscanbeconnectedtoterminals1–8.Class2
circuitsaredenedinArticle725oftheNationalElectricalCode(NFPA70)andSection16
oftheCanadianElectricalCode(C22.1).AClass2circuitisasourcehavinglimitedvoltage
andenergycapacityasfollows:
A.IfanInherentlyLimitedPowerSource,voltageislimitedto30V ACor30VDC,and
energyislimitedto8A.
B.IfnotanInherentlyLimitedPowerSource,voltageislimitedto30V ACor30VDC,
energyislimitedto250V A,andcurrentislimitedto1000/Vmax.Thefuseislimited
to5Aifmaximumvoltageis20V ,or100/Vmaxifvoltageisgreaterthan20V
butlessthan30V .
990–1611C-001
EmergencyPowerOffSystemInstallationandOperation