Technical data
Scalable Solution for Critical Environments
APC NetworkAIR™ FM-DX 5
Glycol-Cooled Configuration
Glycol-cooled systems are completely charged
and factory tested in a sealed system for reliabil-
ity. In mid to low ambient climates, an
economizer coil can be used to increase effi-
ciency and extend compressor life. Economizer
operation greatly reduces the energy consump-
tion of the system. Water regulating valves
control head pressure.
• System is used with a fluid cooler.
• Factory tested as a sealed system.
• Eliminates the need for field refrigerant piping.
• No requirement for water treatment.
• Economizer option for high efficiency.
• Low maintenance.
Water-Cooled Configuration
Water-cooled systems are completely charged
and factory tested as a sealed system for reliabil-
ity. Cooling towers are used as a source of heat
rejection and can be used to serve multiple
indoor units. Towers utilizing outdoor air require
water treatment.
• System used with a cooling tower or other source
of water.
• Factory sealed and tested system.
• Eliminates the need for field refrigerant piping
• Economizer option for high efficiency
Air-Cooled Configuration
Air-cooled systems are not pre-charged from the
factory, requiring field refrigerant piping. Each
installation requires an engineered piping solu-
tion. APC strongly recommends installation by a
highly qualified refrigeration contractor, to
avoid improper elevation and long piping runs.
• System used with a remote air cooled condenser
• Requires field refrigerant piping
• Low maintenance
i
MULTICOOL COIL
(OPTIONAL)
EXPANSION
TANK
PUMP
CONDENSER
COMPRESSOR
FLUIDCOOLER
EXPANSION
VALVE
EVAPORATOR
MULTICOOL COIL
(OPTIONAL)
EVAPORATOR
WATER TOWER
CONDENSER
EXPANSION
VALVE
COMPRESSOR
PUMP
MULTICOOL COIL
(OPTIONAL)
EXPANSION
VALVE
COMPRESSOR
CONDENSER
RECEIVER
EVAPORATOR