Technical data
Guide Specifications
APC NetworkAIR™ FM-DX 51
3.05 MULTICOOL
A. Air, Water and Glycol systems shall have the option of a chilled water coil that is designed to
be the primary cooling source to the backup direct expansion coil. The MultiCool (chilled
water) coil shall be constructed with copper tubes and aluminum fins. It shall be located in the
return air, before the V-Frame evaporator coil. The MultiCool coil shall be rated at ____BTU/
HR (kW) sensible cooling capacity with 45 F (7.2 C) entering water temperature. The
MultiCool coil shall require ____GPM(l/s) of chilled water and the pressure drop shall not
exceed ____psig (kPa).