Performance Specifications—Glycol Cooled
NET COOLING CAPACITY - BTU/HR* FM 35 FM 50
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total 121,000 (35.6) 190,000 (55.6)
Sensible 109,000 (31.9) 161,000 (47.3)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total 112,000 (32.6) 173,000 (50.9)
Sensible 108,000 (31.6) 157,000 (46.0)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total 111,000 (32.6) 175,000 (51.3)
Sensible 111,000 (32.6) 175,000 (51.3)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total 106,000 (31.0) 164,000 (48.0)
Sensible** 104,000 (30.6) 152,000 (44.3)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total 107,000 (31.3) 167,000 (48.9)
Sensible 107,000 (31.3) 167,000 (48.9)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total 103,000 (30.0) 159,000 (46.6)
Sensible 100,000 (29.3) 148,000 (43.3)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total 103,000 (30.0) 161,000 (47.3)
Sensible 103,000 (30.0) 161,000 (47.3)
NET DEHUMIDIFICATION MODE CAPACITY - BTU/HR (kW)
72F DB, 62.7F WB (22.2C DB, 17.1C WB) 60% RH
Total - 1 Compressor 53,000 (15.6) 84,000 (24.6)
Sensible - 1 Compressor 49,000 (14.3) 73,000 (21.3)
Total - 2 Compressors 102,000 (29.9) 153,000 (44.6)
Sensible - 2 Compressors 72,000 (21.0) 103,000 (30.0)
72F DB, 61.4F WB (22.2C DB, 16.3C WB) 55% RH
Total - 1 Compressor 52,000 (15.3) 85,000 (24.9)
Sensible - 1 Compressor 52,000 (15.3) 85,000 (24.9)
Total - 2 Compressors 99,000 (29.0) 149,000 (43.6)
Sensible - 2 Compressors 78,000 (22.9) 112,000 (32.9)
70F DB, 59.7F WB (21.1C DB, 15.4C WB) 55% RH
Total - 1 Compressor 51,000 (14.9) 82,000 (23.9)
Sensible - 1 Compressor 51,000 (14.9) 82,000 (23.9)
Total - 2 Compressors 96,000 (28.0) 146,000 (42.6)
Sensible - 2 Compressors 78,000 (22.9) 112,000 (32.9)
MULTICOOL -- NET COOLING CAPACITY DATA -- BTU/HR (kW) - 45F (7.2C) EWT*
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total 183,000 (53.6) 254,000 (74.3)
Sensible 140,000 (41.3) 196,000 (57.3)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total 147,000 (43.3) 205,000 (60.0)
Sensible 129,000 (37.9) 181,000 (52.9)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total 144,000 (42.0) 200,000 (58.3)
Sensible 137,000 (40.0) 191,000 (55.9)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total 126,000 (36.9) 179,000 (52.6)
Sensible** 120,000 (35.0) 167,000 (48.9)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total 120,000 (35.3) 168,000 (49.3)
Sensible 120,000 (35.3) 168,000 (49.3)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total 117,000 (34.3) 162,000 (47.6)
Sensible 112,000 (32.9) 156,000 (45.6)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total 110,000 (32.3) 154,000 (45.3)
Sensible 110,000 (32.3) 154,000 (45.3)
MULTICOOL REQUIREMENTS - CHILLED WATER, 45F (7.2C) EWT
Water In -- GPM (L/s) 28.0 (1.8) 44.0 (2.8)
Pressure Drop -- PSI (kPa) 6.6 (45.5) 15.2 (104.8)
*Rated Capacity +/-10%
**Nominal Rating Point