Technical data

10 APC NetworkAIR™ FM-DX
Microprocessor Controller
Microprocessor Controller
The microprocessor controller is
standard on each system. The con-
troller provides precision control
for the demanding requirements of:
Data centers
Control rooms
•Clean rooms
Switch rooms
UPS rooms
The easy-to-use display allows the
operator to select options from the
device’s menu-driven interface to
control and monitor the connected
air conditioning system.
Open Architecture
The NetworkAIR FM protocol is
open for integration with all build-
ing management systems.
Communication interface on the
system can be MODBUS RTU
RS485.
Control Type
Controller utilizes proportional and
integral derivative (PID), a time
proven precision environmental
control method. This allows for
custom tuning of control variables
to achieve desired system response.
Functions
Status Report
System Control
Event Logging
Redundant Unit Group
Static Pressure Adjustment
Logging
The microprocessor displays the 64
most recent alarms. Each alarm log
contains a time/date stamp as well
as operating conditions at the time
of occurrence. The controller also
displays run time, in hours, for
major components (compressors,
heaters, humidifier, blower motors).
Control
The backlit, four-line x twenty-
character display is password
configurable.
Temperature Setpoint 60-90° F
(15-32
° C)
Humidity Setpoint 30-80% R.H.
Blower Motor Setpoint 20-60Hz.
(Factory preset for model size and
options.)
High Temperature Alarm 35-90
° F
(2-32
° C)
Low Temperature Alarm 35-90
° F
(2-32
° C)
High Humidity Alarm 15-85% RH
Low Humidity Alarm 15-85% RH
Customer Interface Modules
Each unit comes equipped with up
to 3 additional discrete input/output
modules. Each interface module is
programmable with outputs that can
map from any system alarm through
the microprocessor controller.
Inputs are capable of mapping to
outputs as a system alarm or custom
alarm.
Alarms
High control temperature
Low control temperature
High control humidity
Low control humidity
Clogged filter
Return sensor failure
High supply temperature
Low supply temperature
Loss or low airflow
Loss of water flow
Supply sensor failure
Water regulator actuator failure
Econ/MultiCool Actuator failure
High head pressure
Low suction pressure
Humidifier failure
Replace humidifier canister
Frequency controller failure
Air block interlock open
Water detected
Fire (thermal sensor trip)
Smoke detected
Condensate pump failure
Alarm LED
Warning LED
Check Log LED
System On LED
Liquid Crystal Display (LCD)
Menu Selection scroll keys
ESC key
Enter key
Help key