8 Service, Accessories & Spares
8.1 Rectifier replacement
If a faulty rectifier is to be replaced simply unscrew the two front panel fixings on the rectifier front panel
and withdraw the rectifier from the shelf. A replacement rectifier can then be inserted directly into the
shelf and will start-up automatically.
Note – The rectifiers are “hot plugable” and therefore can be replaced without turning the system off.
8.2 Alarms Card replacement
If the alarms card is to be replaced turn off all supplies to the MX06 by operation of the relevant
disconnection devices. Then simply unscrew the single earthing screw and the four rear cover screws.
Remove the rear cover and then unplug the alarms card. A replacement card can then be inserted
directly into the shelf and will start-up automatically when power is reconnected.
Note – The system can be operated without the alarms card but all alarm and control functions will be
unavailable.