Datasheet

User Manual 990-9189A
DC MX06 60A Shelf Page 23 of 30 18
th
FEB 02
4.2 System Output Connection
The DC MX06 60A Shelf has an output voltage of 54.5Vdc nominal. In standard configuration the
positive output is connected to earth. This means the output is –54.5Vdc with respect to earth.
The picture directly below shows the output bus-bars and the connection points where output cables
should be connected. The bus-bar inserts are M6 threaded therefore output cables should be crimped
with M6 crimps. The cables should be connected to the bus-bars using the supplied M6 hex head
screws with flat and spring washers.
The maximum output current available from the DC MX06 60A Shelf is 63A, cables used should be
rated accordingly and colour coded as to meet local installation regulations.
0V Bus-bar - 54V Bus-bar
Co
nn
ect
i
o
n P
o
in
t
Co
nn
ect
i
o
n P
o
in
t
Use supplied M6
hex head screw to
fix output cables