DC MX06 60A Shelf Page 14 of 30 18
th
FEB 02
2.4 System Set-up options
2.4.1 Current Limit Programming
The system output current limit can be set to either the standard “High” (100%) level or “Low” (70%)
level by using SK30.
For “High” current limit level link pins 1 and 2
For “Low” current limit level link pins 2 and 3
Selecting “Low” current limit level will program down each rectifiers current limit level to roughly 70% of
the default level. (See section 2.1.1 for default levels).
System is set to “High” current limit as standard.
2.4.2 Enable Function
The system can be set to either “Local” or “Remote” Enable by using SK29.
For “Local” enable link SK29 pins 2 and 3 with supplied link.
For “Remote” enable link SK29 pins 1 and 2 with supplied link.
If “Remote” enable SK4-19 and SK4-10 must be linked to enable rectifier outputs.
System is set to “Local Enable” as standard.
SK30
SK29
Remove rear cover
to leave view shown