User Manual

Back-UPS BR900G-RS Installation and Operation
9
Specifications
t
Model BR900G-RS
VA 9 00 VA
Maximum Load 540 W
Nominal Input Voltage 230 V
Online Input Voltage Range 176 V to 294 V
Automatic Voltage Regulation 188 V-216 V +11.2%
252 V-282 V -11.2%
Frequency Range 50/60 Hz ± 1 Hz
On-battery wave shape Step-approximated sine-wave
Typical Recharge Time 8 hours
Transfer Time 10 ms, maximum
Operating Temperature 0° to 40°
C (32° to 104°F)
Storage Temperature -15° to 45° C (5° to 113° F)
Unit Dimensions 25 × 10 × 38.2 cm (9.8 × 3.9 × 15 in)
Unit Weight 11 kg (24 lbs)
Interface Serial, USB
On-Battery Runtime Go to: www.apc.com
Replacement Battery The battery cartridge typically lasts 3 to 6 years. Environmental factors impact
battery life. High temperatures, poor quality A/C power, and frequent, short
deration discharges will shorten battery life. To order replacement battery cartridge
APCRBC123, refer to the APC Web site, www.apc.com.
Recycle used battery cartridges.
Humidity 0 to 95% relative humidity, non-condensing
Pollution degree 2
Overvoltage category II
Applicable power grid power
distribution system
TN Power system
Applicable standard IEC 62040-1
International Protection Code IP20