Detected System Errors
The Back-UPS will display these error messages. Except for errors F01 and
F02, contact SEIT Technical Support.
If these icons are flashing... This may be the problem.
The Back-UPS is overloaded. Disconnect one of the items connected to
the Back-UPS. If the Overload icon stops flashing, the Back-UPS is no
longer overloaded and will continue to operate normally.
The Back-UPS is operating on AC power, but the battery is not
functioning properly. Contact Schneider Electric IT (SEIT) Customer
Service to order a replacement battery. See “Replacement Battery” on
page 11.
The Back-UPS is operating on battery power and the battery power is
getting low. Shut down all connected equipment to avoid losing an
unsaved data. When possible, connect the Back-UPS to AC power to
recharge the battery.
The battery is not connected. See “Connect the Battery on page 2 to
make sure battery wires are connected properly.
F01 On-Battery
Overload
Turn the Back-UPS off.
Disconnect non-essential
equipment from the Battery
Backup outlets and the turn
Back-UPS on.
F02 On-Battery
Output
Short
Turn the Back-UPS off.
Disconnect all equipment from
the Battery Backup outlets and
the turn Back-UPS on.
Re-connect equipment one item
at a time. If the output is tripped
again, disconnect the device that
caused the detected error.
F04 Clamp Short
Errors F04-F09 cannot be
corrected by the user, contact
SEIT Technical Support for
assistance.
F05 Charge Error
F06 Relay Welding
F07 Temperature
F08 Fan Error
F09 Internal Error
bu088d