User Manual
Table Of Contents
- Important Safety Information
- Product Handling Guidelines
- Safety and General Information
- Inventory
- Connect the Battery
- Wall Mount Installation
- Panel Features
- Specifications
- Turn On the Back-UPS
- Turn Off the Back-UPS
- Mute
- UPS Self Test
- PowerChute™ Personal Edition Software
- Status Indicators
- Voltage Sensitivity Adjustment (Optional)
- Replace Battery
- Troubleshooting
- Warranty
- Service
- APC by Schneider Electric IT Customer Support Worldwide
- User Manual Back-UPS™ BE650G2-IT and BE850G2-IT
Back-UPS BE650G2-IT/BE850G2-IT
7
Specifications
BE650G2-IT BE850G2-IT
Input Voltage 220 - 240 Vac
Frequency 47 to 63 Hz
Brownout Transfers 180 Vac Typical
Over-voltage Transfer 266 Vac Typical
Output UPS Capacity 650 VA, 400 W 850 VA, 520 W
Battery Backup outlets 2.96 A 3.87 A
Total Amperage 6 A
Voltage - On Battery 230 Vac ± 8%
Frequency - On Battery 50/60 Hz ± 1 Hz
Transfer Time 6 milliseconds Typical, 10 milliseconds
maximum
USB Port * Charging Rating 5 V; 2.40 A
Charger compatibility USB Battery Charging Specification 1.2
* Power output is dependent on the power drawn by the connected device.
Check with the device manufacturer to understand the maximum charging
current for a given USB specification.
Protection and
Filtering
AC Surge Protection Full time, 310 Joules
EMI/RFI Filter Full time
Utility Power Input Resettable circuit breaker
Battery Type Sealed, maintenance-free, lead acid 12 V
Average Life 3 - 5 years, depending upon the number
of discharge cycles and environmental
temperature
Charging Time 16 hours.
Using the USB port while charging the
battery will increase the battery charging
time
Physical Net Weight 8.8 lb (4 kg) 9.9 lb (4.5 kg)
Dimensions
L x W x H
14.4 in x 5.1 in x 4.7 in
36.5 cm x 13 cm x 12 cm
Environmental Operating Temperature 32 ºF to 104 ºF (0 ºC to 40 ºC)
Storage Temperature 5 ºF to 113 ºF (-15 ºC to 45 ºC)
Operating Relative Humidity 0 to 95% non-condensing humidity
Pollution degree 2
International Protection Code IP20
Overvoltage category II
Applicable power grid power distribution system TN Power system
Applicable standard IEC 62040-1