APC BC300 Series 40kW 208/450/480V User Guide Copyright ©2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor
Thank You Thank you for choosing the APC BC Series. Please read this User Guide thoroughly prior to using the system as it provides important information on safe and efficient use. The use of this product must comply with national, federal, state, municipal and local codes. IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS Safety Symbols used in this manual WARNING! Indicates a hazard which, if not avoided, could result in injury or death.
Contents: 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 Introduction 4 1.1 4 Display Unit UPS Stop/Start 5 2.1 2.2 5 5 UPS Stop (for stand-by) UPS Start (from stand-by) Operation 6 3.1 3.2 3.3 7 8 9 Operation Modes Using the Keys Displaying Measurements Parameter Settings 11 Alarms and Events 13 5.1 5.2 5.3 5.4 13 13 14 23 Silencing the Audible Alarm Displaying the Alarm Log Alarm Messages Displaying the Events Log Maintenance and Testing 24 6.1 6.2 6.
Introduction 1.0 Introduction This UPS system is designed to offer reliable and problem-free power supply for several years. The system requires only a minimum of maintenance, but we recommend you follow the maintenance guidelines described in the “Maintenance & Testing” section of this User Guide. 1.1 Display Unit The display unit (located on the front of the UPS) is the link between the user and the UPS and consists of a display, an alarm LED indicator and a keyboard.
UPS Stop/Start 2.0 UPS Stop/Start WARNING! AC voltage generated either from batteries or utility may be present at UPS output. Always disconnect AC input supply source, switch off UPS, AND switch off DC. TEST BEFORE YOU TOUCH! Some UPS systems have a factory-set auto-start feature, which automatically switches on the UPS whenever utility supply is switched on (AC line). See the “Parameter Settings” section in this User Guide for instructions on how to de-activate this function.
Operation 3.0 Operation The keyboard is used to program and control parameters and to display alarm messages and measured values.
Operation 3.1 Operation Modes The display automatically indicates which mode the unit is operating in. See Table 1 below for sample display messages and an explanation of each. Table 1: Operating Modes Sample Display Mode Operation Mode Description Normal Operation load power ##% The UPS is in the normal operation mode. During normal operation, utility (AC line) passes through the UPS and to the load. The inverter regulates the output and charges the batteries.
Operation 3.2 Using the Keys Table 2: Using the keys Key Function Scroll up through lists of e.g. parameters, alarms, or events. Scroll down through lists of e.g. parameters, alarms, or events. Key Function Display the time and date. If the unit is in the parameter mode, use this key to change the setting of a parameter from “OFF” to “ON.” Display inverter current. Enter a value or exit a mode. Display output frequency. Display the alarm log.
Operation 3.3 Displaying Measurements The APC BC300 Series UPS measures several values during operation that you can display by pressing one or two keys. This section illustrates how to display the measurements, what a sample display of each measurement looks like, and what the display reads. If two keys are shown, press those keys simultaneously. The display values shown below are samples only. Table 3: Display Measurements (Examples) Key Sample Display Description Utility 1.
Operation When two keys are shown, press those keys simultaneously. Keys Sample Display Description Battery temp. 25° C Battery temperature is 77° F (25° C) Output peak curr 19 19 19 Aac Output peak current is 3 x 19 Aac. Normal operation load power xx% 01.12.16 10.22.13 UTC Returns to “Normal operation” display and indicates the% load of the most fully loaded phase (leg). Year, month, day. Hour, minute, second. UTC = Universal Time Coordination. (This may be programmed to your time.
Parameter Settings 4.0 Parameter Settings User parameters allow you to define the UPS settings. You can view and program the parameters listed in Table 2 below. The parameters are easy to access and program: simply follow the five steps below. NOTICE! Make sure that you fully understand a parameter before changing it. Call APC Technical Support or your nearest APC office for assistance. 1. Press to display the user parameter list. 2. or Press to scroll through the list. 3.
Parameter Settings Table 4: Parameter Settings PARAMETER FACTORY SETTING DESCRIPTION Second Language OFF If you select ON, the APC BC300 Series displays all messages in its second language (Spanish). Adaptive slewrate ON OFF is used when utility frequency is unstable. Call APC Technical Support before changing this parameter. Battery monitor reset — Choose ON to reset the battery monitor alarm and remove battery monitor alarm messages from the alarm log and to reset all battery information (e.g.
Alarms and Events 5.0 Alarms and Events Alarms are indicated by a red light (above the left-hand corner of the display) and a 30-second acoustic signal. An alarm is registered in the alarm log as long as it is present. All alarms are also registered in an event logger and remain there in a stack with room for 250 events. The events are stored in order of occurance, with the latest event appearing first. 5.
Alarms and Events 5.3 Alarm Messages Table 5: Possible Alarms Alarm Message Description Action Battery MCB is off The battery breaker is open. If bypass voltage is within tolerance, the unit transfers to static bypass operation. If not, the unit transfers to stand-by and does not supply output voltage. At the battery breaker, set the precharge/discharge switch to the precharge position and hold it in this position until the LED turns off.
Alarms and Events Table 5: Possible Alarms Charge reg. error (reg. = regulator) Failure in charge regulation. The unit transfers to battery until the “Low DC shutdown” alarm occurs; then, it transfers to stand-by and does not supply output voltage. Call APC Global Service. External service switch activated The external service bypass switch is in the line position. The unit is in stand-by and does not supply output voltage. However, the loads may be receiving power from the external manual bypass.
Alarms and Events Table 5: Possible Alarms High output voltage (This alarm is usually only listed in the events log) The output voltage is higher than the alarm setting. The unit stays in the normal operation mode. If the alarm is not cleared, the unit will transfer to static bypass operation if bypass is within tolerance. If bypass is not within tolerance, the unit will transfer to stand-by and will not supply output voltage.
Alarms and Events Table 5: Possible Alarms Low DC shutdown (This alarm is normal when the UPS has run on battery for a long time) The UPS has been running on battery power because of a power outage or problems in the AC input. Battery voltage has dropped below the shutdown setting, and the UPS has shut down. If bypass is within tolerance, the unit will transfer to static bypass operation. If not, the unit will transfer to stand-by and will not supply output voltage.
Alarms and Events Table 5: Possible Alarms Mains is out of tolerance (This alarm occurs during a power outage) The utility (AC input) voltage is too high or too low, so the unit transfers to battery operation. If AC input returns to normal, the unit transfers back to normal operation. If not, the unit continues to run on battery until the “Low DC shutdown” alarm occurs. Then, if bypass voltage is within the range programmed into the UPS, the unit transfers to bypass.
Alarms and Events Table 5: Possible Alarms Output is out of tolerance The output voltage is too high or too low (out of tolerance). If the alarm was caused by high output voltage, the unit transfers to static bypass operation if bypass is within tolerance. If bypass is not within tolerance, the unit transfers to stand-by and does not supply output voltage. If the alarm was caused by low output voltage, the unit transfers to static bypass operation if bypass is within tolerance.
Alarms and Events Table 5: Possible Alarms Static switch 1 temp. warning The temperature on the heat-sink for the main static switch is higher than the warning setting. The unit’s status does not change. However, if the temperature continues to rise, the unit will sound a “Static switch 1 temp. shutdown” alarm. Find the vents for the UPS fans and check to see if the fans are operating. Do not try to open the unit, and do not insert anything into a fan vent.
Alarms and Events Table 5: Possible Alarms TSM 1 temp. shutdown Inverter module 1 has shut down because the temperature on the heat-sink is higher than the shutdown level. If bypass is within tolerance, the unit transfers to static bypass operation. If not, the unit transfers to stand-by mode and does not supply output voltage. Find the vents for the UPS fans and check to see if the fans are operating. Do not try to open the unit, and do not insert anything into a fan vent.
Alarms and Events Table 5: Possible Alarms TSM 3 temp. shutdown Inverter module 3 has shut down because the temperature on the heat-sink is higher than the shutdown level. If bypass is within tolerance, the unit transfers to static bypass operation. If not, the unit transfers to standby and does not supply output voltage. Find the vents for the UPS fans and check to see if the fans are operating. Do not try to open the unit, and do not insert anything into a fan vent.
Alarms and Events 5.4 Displaying the Events Log The events log is a list of the last 250 alarms and operational modes. This log includes the time and date of each event. Most entries in this log will be alarms (see the “Alarms and Events” section in this User Guide for a description of alarms). Other entries describe operating modes (see the “Operation Modes” section in this User Guide for details); the table below lists and describes these Event Log messages. 1. To access the events log, press both 2.
Maintenance and Testing 6.0 Maintenance and Testing APC recommends a periodic preventive maintenance check every six months. APC also recommends that the cooling fans be replaced every three years. 6.1 Preventive Maintenance Check At the preventive maintenance check, a qualified service technician should: • Check all wiring connections. • Inspect and clean the unit. • Check the batteries. • Check the AC and DC meter functions. • Perform a battery capacity or battery monitor test.
Maintenance and Testing To perform a battery monitor test: 1. Press to display the user parameters. 2. Press test.” or 3. Press min.” to start the battery monitor test. The display shows “Batt. operation time > xxx to scroll through parameters until the display shows “Battery monitor (“xxx” = the minutes of runtime remaining. This number will fluctuate during the test.) 4. When the test is complete, the display will show “Normal operation load power xx%” if the batteries are in acceptable condition.
Maintenance and Testing a. Display the user parameter list by pressing . b. Use the arrow keys to scroll through the parameters until the display shows “Battery capacity test: xxx.” c. Switch the battery capacity test “OFF” by pressing . 5. Wait until the display shows “Normal operation load power xx%” and a short alarm sounds. 6. Press . The display will show “Battery capacity test: xxx.” (“xxx” = the estimated backup time in minutes) 7. Press to exit the user parameter list.
Start-up and Shutdown Procedure 7.0 Start-up and Shutdown Procedure 7.1 Start-up from Maintenance Bypass This section contains instructions on how to start the UPS from maintenance bypass. The steps in this procedure apply to units with an APC-supplied Maintenance Bypass Panel. 1. Make sure that the following switches are in the following positions: The UPS AC disconnect switch should be “OFF”. The UPS bypass switch should be on “LINE”. The battery breaker should be “OFF”. 2.
Start-up and Shutdown Procedure This section contains information on how to shut down the UPS from normal operation mode. This procedure applies to units with an APC-supplied Maintenance Bypass Panel. 1. If you have shut the loads down: Move on to step 2. If the loads are to remain powered: Program the unit into static bypass operation: a. Press to access the user parameters. b. Press the c. Press to turn static bypass operation on. The display should show “Bypass operation”. d.
Specifications 8.0 Specifications For a complete list of specifications, see the APC BC300 Series Installation Guide. Table 7: General Specifications Utility tolerance +10%, —15% (programmable) Bypass tolerance ±10% (programmable) Input frequency ±6% (programmable) 60 Hz Output frequency - utility synchronized: 60 Hz ±6% - free running: 60 Hz ±0.1% Current distortion 0-5% Tolerance - symmetrical load: ±1%, static. - asymmetrical load: ±3%, static.
Specifications For Users in Canada This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Options 9.0 Options APC offers many options for the APC BC300 Series UPSs. For more information, contact your local APC office. Note that some options only apply to certain models. 9.1 Optional Hardware and Software Features 9.1.1 Battery Temperature Compensation: Enables the UPS to adapt the charging voltage to the battery temperature. This is for units with external batteries and this option monitors the temperature in one battery cabinet. 9.1.
Options 9.2.2 Preventive Maintenance Visit Provides a single visit to examine the status and health of the APC system, to ensure proper operation over time. A visual and electronic inspection is performed to ensure that the system is performing to all defined technical and environmental specifications. The service is performed during normal business hours. 9.2.3 On-Site Service Provides 1-year On-Site Repair Service on APC equipment and 7x24 Telephone Technical Support. Response time differs by contracts.
WARRANTY 10.0 WARRANTY 10.1 Life Support Policy As a general policy, American Power Conversion (APC) does not recommend the use of any of its products in life support applications where failure or malfunction of the APC product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. APC does not recommend the use of any of its products in direct patient care.
WARRANTY AND REMEDIES. THE WARRANTIES SET FORTH ABOVE, CONSTITUTE APC’S SOLE LIABILITY AND PURCHASER’S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APC’S WARRANTIES RUN ONLY TO PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.
How to Contact APC 11.0 How to Contact APC APC Corporate 132 Fairgrounds Road West Kingston, RI 02892 USA Tel.: Fax: +1 401 789-5735 +1 401 789-3710 Pre-sales Technical Support +1 877-474-5266 Post-sales Technical Support +1 877-287-7835 Web: www.apc.
How to Contact APC 990-1403 36 User Guide APC BC300 Series 40kW 208/450/480V UPS