Specifications

Back-UPS Pro 500 BG500 120 Vac38
Outlet On / Off / Reboot
Path: Outlet > On / Off / Reboot
Turn on, turn off, or restart outlets with
this option.
You can select any of the following
actions (or no action) for each outlet.
These are one-time actions.
When the state of the outlet is
off:
–On
When the state of the outlet is
on:
–Off
Reboot: Turn off the outlet immediately then turn it on after a few seconds
After you select an action, click Next>> to view a detailed description of the action, including the duration of any
delays. Click Apply to commence the action.
Watchdog Settings
Path: Outlet > Watchdog Settings
Under the Web page “Outlet >
Settings”, when this Watchdog is set to
‘Yes’, the Smart Outlet will operate in
Watchdog mode.
In Watchdog mode, the Smart Outlet is
configured to periodically confirm that
a Test Target IP Address (such as a
server, computer, modem, router, etc.) is
working by sending ping requests to the
address.
The UPS expects a response after each
ping. If it fails to get the response for the
duration of a Test Interval (in “Outlet >
Watchdog Settings” page), it is assumed
that the device is not functioning
properly. The UPS will attempt to
restore the device to normal operation by power cycling the Watchdog enabled outlet.
The user has to provide the Time to Boot Device value to boot the device properly after the device is powered on.
After the Time to Boot Device has lapsed, the UPS will start to ping the device.
If the UPS still fails to ping the target IP Address and reboots to the point that it reaches the Max Reboot Attempts,
the Watchdog mode will then be disabled. The UPS will re-start pinging the target IP Address depending on the
Reactivate Watchdog setting.
In Watchdog mode, users still have the ability to manually reboot the device from a remote location over the
network.