Specifications

Back-UPS BX800CI-RS/BX1100CI-RS Installation and Operation
7
Specifications
Specification BX800CI-RS BX1100CI-RS
Input Voltage 230 Vac, nominal
Frequency 50 Hz
±3 Hz, 60 Hz ±3 Hz
Brownout Transfer 155 Vac, typical
Over-voltage Transfer 280 Vac, typical
Output U P S C a p a c i t y ( t o t a l ) 8 0 0 V A / 4 8 0 W 11 0 0 V A / 6 6 0 W
Voltage On Battery 230 Vac rms (step-approximated sinewave)
Frequency on Battery 50 Hz
±1 Hz, 60 Hz ±1 Hz
Transfer Time 8 ms typical
Protection and
Filtering
AC Surge Protection Full time, 273 Joules
AC Input Resettable circuit breaker
Battery Type (maintenance free) 12 V 9 Ahr Each battery 12 V 7.2 Ahr
Average Life 2 - 5 years depending on the number of discharge cycles and
environmental temperature
Typical Recharge Time 8 Hours
Physical Net Weight 8 kg 12 kg
Dimensions (H x W x D) 21.5 cm x 13 cm x 33.6 cm
Operating Temperature 0
o
C to 40
o
C (32
o
F to 104
o
F)
Storage Temperature -15
o
C to 45
o
C (5
o
F to 113
o
F)
Operating Relative Humidity 0 to 95% non-condensing
Operating Elevation 0 to 3000 m (0 to 10,000 ft)