User`s guide
®
USER’S GUIDE
AUTOMATIC TRANSFER SWITCH
173
a. Select option 3—System
b. Select option 4—File Transfer
c. Select option 2—
XMODEM
d. Type Yes at the prompt to continue with the transfer.
7. Select the appropriate baud rate. A higher baud rate causes faster
firmware upgrades. Also, change the terminal program’s baud rate to
match the one you selected, and press
ENTER.
8. From the terminal program’s menu, select the binary AOS file to
transfer via XMODEM-CRC. After the XMODEM transfer is complete,
set the baud rate to 9600. The Automatic Transfer Switch will
automatically restart.
9. Repeat step 3 through step 8 to install the application module. In step
8, substitute the application module file name for the AOS module file
name.
For information about the format used for application
modules, see Firmware files (Automatic Transfer Switch).