Specifications

Specifications: ATS with Power Distribution
Automatic Transfer Switch with Power Distribution 77
Environmental
Operating Temperature Range 23 to 104°F / –5 to 40°C; The average temperature over a
24-hour period should not exceed 95°F/35°C.
Operating Relative Humidity 5 to 95%, non condensing
Operating Elevation 0 to 6,562ft /0 to 2000m
Storage Temperature Range –13 to 131°F / –25 to 55°C; The average temperature over a
24-hour period should not exceed 158°F/70°C
Storage Relative Humidity 5 to 95%, non condensing
Storage Elevation 0 to 49,200ft / 0 to 15000m
Compliance
Safety UL & cUL Listed to UL 67 (UL1008 for ATS)
Emissions FCC Verified Class A, Per standard FCC 47 CFR Part 15
Electrostatic Discharge (ESD) IEC 61000-4-2
Electrical Fast Transients (EFT) IEC 61000-4-4
Surge Transient IEC 61000-4-5
Continuous Electromagnetic Susceptibility IEC 61000-4-3